Plan REJECTED for 4500 repair garage going to be converted to service CHG repair vehicles. Reviewed using FFPC 5th edition. NFPA 1 ch 30 and NFPA 52
Reviewer: Sandra Boike 904 209 1741 sboike@sjcfl.us
To reply to comments and/or resubmit plans, contact your permit tech via their email or call 904-827-6800. To help speed the review process you may include a written comment response summary to clarify or illustrate where corrections were made on plans. Please remember to use the Florida Fire Prevention Code 5th Ed for all code reference in a response to comments. The fire plans examiner does not use or have a copy of the Florida Building Code.
To schedule your fire inspection please call 904 209 1740x1.
|
| |
|
|
NFPA 1.30.2.4 Means of egress. Please provide illustrate exit identification.
|
| |
|
|
NFPA 1.30.2.8. Gas detection, please provide manufacture cut sheets for the components of the detection systems. Please provide order of operation of the system.
|
| |
|
|
NFPA 1.30.2.8.4 Monitoring of the detection system shall be in accordance with NFPA 72. How are you meeting this?
|
| |
|
|
Could not locate return air openings? NFPA 1.30.2.9.2
|
| |
|
|
Will there be any containers to store the NG during repair or will there be a process of removing/ refueling the equipment? NFPA 52.4
|
| |
|
|
Is there a 2 hr separation from the repair/ storage of the vehicles containing NG and the other rooms? NFPA 52.8.4.3.4.2
|
| |
|
|
How are you compiling with NFPA 52.8.4.3.4.5 or 8.4.3.4.6?
|
| |
|
|
Please illustrate the placement of fire extinguishers. NFPA 1.30.3.2.2 and NFPA 58.8.15
|
| |
|
|
Hazard Classification appears to have changed. Please provide classification from the design professional in accordance with NFPA 101.40.1.5, NFPA 101.6.2. This may trigger additional requirements.
|
| |