Plan REJECTED for 4500 repair garage going to be converted to service CHG repair vehicles. Reviewed using FFPC 5th edition. NFPA 1 ch 30 and NFPA 52

Reviewer: Sandra Boike 904 209 1741  sboike@sjcfl.us

To reply to comments and/or resubmit plans, contact your permit tech via their email or call 904-827-6800. To help speed the review process you may include a written comment response summary to clarify or illustrate where corrections were made on plans.  Please remember to use the Florida Fire Prevention Code 5th Ed for all code reference in a response to comments. The fire plans examiner does not use or have a copy of the Florida Building Code.

To schedule your fire inspection please call 904 209 1740x1.

 

NFPA 1.30.2.4 Means of egress. Please provide illustrate exit identification.

 

NFPA 1.30.2.8. Gas detection, please provide manufacture cut sheets for the components of the detection systems. Please provide order of operation of the system.

 

NFPA 1.30.2.8.4 Monitoring of the detection system shall be in accordance with NFPA 72. How are you meeting this?

 

Could not locate return air openings? NFPA 1.30.2.9.2

 

Will there be any containers to store the NG during repair or will there be a process of removing/ refueling the equipment? NFPA 52.4

 

Is there a 2 hr separation from the repair/ storage of the vehicles containing NG and the other rooms? NFPA 52.8.4.3.4.2 

 

How are you compiling with NFPA 52.8.4.3.4.5 or 8.4.3.4.6?

 

Please illustrate the placement of fire extinguishers. NFPA 1.30.3.2.2 and NFPA 58.8.15

 

Hazard Classification appears to have changed. Please provide classification from the design professional in accordance with NFPA 101.40.1.5, NFPA 101.6.2. This may trigger additional requirements.