| 10707472 |
****NEED ELECTRICAL PERMIT FOR 400 AMPS SERVICE & 1 SUB FEED OF 400 AMPS & 1 SUB FEED OF 225 AMPS**** THEN POWER CAN BE RELEASED LET THELMA KNOW WHEN PERMITTED
|
1/29/2008 2:51:47 PM * TGM
|
| 20705284 |
01/11/08 Please do CEILING ELECTRICAL INSPECTION per Nikka 407-298-7430
|
1/10/2008 10:25:48 AM * JRG
|
| 20705284 |
01/11/08 Please do CEILING ELECTRICAL INSPECTION per Nikka 407-298-7430
|
1/10/2008 10:25:48 AM * JRG
|
| 40705266 |
1 AC UNIT 60,000 BTU 10KW
|
12/5/2007 2:54:47 PM * TEB
|
| 20705284 |
WIRING
|
11/28/2007 9:39:29 AM * TEB
|
| 10707472 |
CODE EDITION 2006, TYPE OF CONTRUCTION 5B,
|
11/14/2007 3:21:16 PM * YRM
|
| 10707472 |
FAULT CURRENT 37,880 120/208V 3 PHASE
ELECTRIC 400 AMP 3 PHASE, 2 SUBFEEDERS 1-400 AMPS, 1-225 AMPS 3 PHASE.
MECHANICAL 1-5 TON, PLUMBING 1 WATER HEATER
|
11/14/2007 3:20:14 PM * YRM
|